Chiller Rental

Chiller C2R162 – 169 kW

FLEXY R454B-1_v3

Chiller C2R-162 chilled water unit – 169 kW

The C2R-162 chilled water unit provides a cooling capacity of 169.35 kW at a flow temperature of 15 °C and a return temperature of 20 °C. The system uses the modern refrigerant R454B and requires an electrical connection of 400 V / 3 Ph / 50 Hz. The monthly rental price is available on request.

C2R-162 chilled water unit – 169 kW chiller for industrial process cooling and air conditioning

The C2R-162 chilled water unit is a powerful, air-cooled chiller for industrial process cooling and air conditioning. With a cooling capacity of 169.35 kW at a flow temperature of 15 °C and a wide temperature range from −10 °C to +30 °C, this unit is ideally suited to a wide range of demanding applications. The technical basis for this includes four hermetic scroll compressors and four axial fans on the condensation side.
The C2R-162 has been developed for reliable use in industry, machine cooling and technical processes. Thanks to its robust design and integrated hydronic circuit, this chiller is particularly suitable wherever high operational reliability and precise cooling are required at high performance levels. The technical basis consists of four scroll compressors, an integrated 750-litre buffer tank and an integrated pump with an available operating pressure of 3.22 bar.

Chiller for versatile high-performance cooling applications

Whenever production processes, machines or technical systems need to be cooled reliably, the C2R-162 demonstrates its strengths. The chiller can produce chilled water or glycol mixtures from −10 °C to +30 °C. This makes the unit particularly suitable for applications where specific process temperatures must be kept constant. The relevant operating data is documented in the data sheet; the nominal capacity under standard conditions (12 °C to 7 °C) is 128.20 kW.
Typical areas of application include industrial process cooling, machine and system cooling, and air conditioning in combination with air handling units (AHUs). In addition, the unit is frequently used for technical cooling in production environments or as temporary rental cooling during maintenance, conversion work or failure of existing systems.

Robust cooling technology for industrial use

The C2R-162 is designed as an air-cooled chilled water unit and is equipped with four axial fans. The air-cooled design simplifies integration into existing systems and makes the unit particularly suitable for temporary and mobile applications. With an air flow rate of 62,000 m³/h per fan, the chiller ensures reliable heat dissipation even under demanding operating conditions. Thanks to the quick water connections (Kamlock DN100) and the 125 CEE plug, the cooling unit can be installed and commissioned quickly.
At the same time, operation remains at a very good level for this performance class, with a sound pressure level of 63.5 dB(A) at a distance of 10 m. This is an important advantage, especially when used in commercial or industrial environments.

Powerful hydraulic circuit with integrated tank

A key advantage of the C2R-162 is its integrated hydronic system. The chiller features an integrated 750-litre buffer tank and an integrated pump, delivering a flow rate of 21.98 m³/h (363.3 lpm) at an operating pressure of 3.22 bar.
This allows the chilled water unit to be integrated quickly and reliably into existing cooling circuits. The heat exchanger is embedded in the internal tank. Especially in industrial applications where a cleanly controlled liquid circuit is essential, this equipment is a real advantage.

Modern cooling technology with R454B

The C2R-162 uses the modern refrigerant R454B. Compared with older high-GWP solutions, this refrigerant represents a more future-oriented approach to modern refrigeration systems.
For users, this means modern technology, high efficiency (EER 3.06) and a refrigeration system that reflects the current standard of professional process cooling.

Technical highlights of the C2R-162

Specification Value
Cooling capacity (15 °C flow / 32 °C ambient temperature) 169.35 kW
Nominal capacity (12 °C to 7 °C / 32 °C ambient temperature) 128.20 kW
Temperature range −10 °C to +30 °C
Cooling medium Chilled water or glycol mixtures
Compressors 4 hermetic scroll compressors
Buffer tank Integrated, 750 litres
Flow rate 21.98 m³/h
Operating pressure 3.22 bar
Design Air-cooled with 4 axial fans
Refrigerant R454B
Electrical connection 400 V / 50 Hz / 3 Ph / PE (125 CEE)
Sound pressure level (at 10 m) 63.5 dB(A)
Weight 2,900 kg operating weight, 2,150 kg empty weight
All values are based on the official data sheet and the technical specifications of the C2R-162.

Typical applications for the C2R-162 chiller

The C2R-162 is particularly suitable for industrial cooling processes, machine cooling and air conditioning with AHUs. It is also frequently used for temporary cooling supply during servicing or as replacement and emergency cooling in the event of existing system failures.

Hire the C2R-162 chilled water unit

The C2R-162 chilled water unit is the right choice when reliable rental cooling for process cooling or air conditioning is required in a higher performance range. Thanks to its solid industrial design, high cooling capacity and integrated hydronic system, this chiller is suitable both for temporary use and for planned rental projects.